OperateAlarm Setup

Station Alarm

Station Alarm when Acknowledged
Station Alarm when Acknowledged:

Select TURNS OFF to turn off the Station Alarm when alarms are acknowledged, but not cleared. Select STAYS ON to keep the Station alarm active until all alarms are acknowledged and cleared

Station Alarm Activation
Station Alarm Activation:

Select DELAYED to delay turning on the Station Alarm until the dial chain notification of an alarm has completed without an acknowledgement. Select IMMEDIATE to turn on the Station Alarm as soon as an alarm occurs

Alarm on Trips
Alarm on Trips:

Select ON to activate the Station Alarm for unacknowledged TRIP and CRITICAL alarms. Select OFF to activate the Station Alarm for unacknowledged CRITICAL alarms only

Alarm Settings

Standby pump start
  • Trigger Station Alarm
  • Alarm severity
Standby pump start:

Select Yes to create a Station Alarm based on the Standby Pump Start alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Pump start trip
  • Trigger Station Alarm
  • Alarm severity
Pump start trip:

Select Yes to create a Station Alarm based on the Pump Start Trip alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Pump over-temperature
  • Trigger Station Alarm
  • Alarm severity
Pump over-temperature:

Select Yes to create a Station Alarm based on the Pump Over Temperature alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Pump seal fail
  • Trigger Station Alarm
  • Alarm severity
Pump seal fail:

Select Yes to create a Station Alarm based on the Pump Seal Fail alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Level sensor fail
  • Trigger Station Alarm
  • Alarm severity
Level sensor fail:

Select Yes to create a Station Alarm based on the Level Sensor Fail alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Pump stop failure
  • Trigger Station Alarm
  • Alarm severity
Pump stop failure:

Select Yes to create a Station Alarm based on the Pump Stop Failure alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Phase failure
  • Trigger Station Alarm
  • Alarm severity
Phase failure:

Select Yes to create a Station Alarm based on the Phase Failure alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Maximum continuous run time
  • Trigger Station Alarm
  • Alarm severity
Maximum continuous run time:

Select Yes to create a Station Alarm based on the Maximum Continuous Run Time alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Maximum starts per hour
  • Trigger Station Alarm
  • Alarm severity
Maximum starts per hour:

Select Yes to create a Station Alarm based on the Maximum Starts per hour alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Intrusion alarm
  • Trigger Station Alarm
  • Alarm severity
Intrusion alarm:

Select Yes to create a Station Alarm based on the Intrusion alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Input supply low
  • Trigger Station Alarm
  • Alarm severity
Input supply low:

Select Yes to create a Station Alarm based on the Input Supply Low alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

High pump current
  • Trigger Station Alarm
  • Alarm severity
High pump current:

Select Yes to create a Station Alarm based on the High Pump Current alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Low pump current
  • Trigger Station Alarm
  • Alarm severity
Low pump current:

Select Yes to create a Station Alarm based on the Low Pump Current alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Backup float reached alarm
  • Trigger Station Alarm
  • Alarm severity
Backup float reached alarm:

Select Yes to create a Station Alarm based on the Backup float reached alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Sump Fail
  • Trigger Station Alarm
  • Alarm severity
Sump Fail:

Select Yes to create a Station Alarm based on the Sump Fail alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

Pump Fail
  • Trigger Station Alarm
  • Alarm severity
Pump Fail:

Select Yes to create a Station Alarm based on the Pump Fail alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.

High level alarm
  • Trigger Station Alarm
  • Alarm severity
High level alarm:

Select Yes to create a Station Alarm based on the High level alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.