Alarm Setup
Station Alarm
Station Alarm when Acknowledged
Station Alarm when Acknowledged:
Select TURNS OFF to turn off the Station Alarm when alarms are acknowledged, but not cleared. Select STAYS ON to keep the Station alarm active until all alarms are acknowledged and cleared
Station Alarm Activation
Station Alarm Activation:
Select DELAYED to delay turning on the Station Alarm until the dial chain notification of an alarm has completed without an acknowledgement. Select IMMEDIATE to turn on the Station Alarm as soon as an alarm occurs
Alarm on Trips
Alarm on Trips:
Select ON to activate the Station Alarm for unacknowledged TRIP and CRITICAL alarms. Select OFF to activate the Station Alarm for unacknowledged CRITICAL alarms only
Alarm Settings
Standby pump start
- Trigger Station Alarm
- Alarm severity
-
-
Standby pump start:
Select Yes to create a Station Alarm based on the Standby Pump Start alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Pump start trip
- Trigger Station Alarm
- Alarm severity
-
-
Pump start trip:
Select Yes to create a Station Alarm based on the Pump Start Trip alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Pump over-temperature
- Trigger Station Alarm
- Alarm severity
-
-
Pump over-temperature:
Select Yes to create a Station Alarm based on the Pump Over Temperature alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Pump seal fail
- Trigger Station Alarm
- Alarm severity
-
-
Pump seal fail:
Select Yes to create a Station Alarm based on the Pump Seal Fail alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Level sensor fail
- Trigger Station Alarm
- Alarm severity
-
-
Level sensor fail:
Select Yes to create a Station Alarm based on the Level Sensor Fail alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Pump stop failure
- Trigger Station Alarm
- Alarm severity
-
-
Pump stop failure:
Select Yes to create a Station Alarm based on the Pump Stop Failure alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Phase failure
- Trigger Station Alarm
- Alarm severity
-
-
Phase failure:
Select Yes to create a Station Alarm based on the Phase Failure alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Maximum continuous run time
- Trigger Station Alarm
- Alarm severity
-
-
Maximum continuous run time:
Select Yes to create a Station Alarm based on the Maximum Continuous Run Time alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Maximum starts per hour
- Trigger Station Alarm
- Alarm severity
-
-
Maximum starts per hour:
Select Yes to create a Station Alarm based on the Maximum Starts per hour alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Intrusion alarm
- Trigger Station Alarm
- Alarm severity
-
-
Intrusion alarm:
Select Yes to create a Station Alarm based on the Intrusion alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Input supply low
- Trigger Station Alarm
- Alarm severity
-
-
Input supply low:
Select Yes to create a Station Alarm based on the Input Supply Low alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
High pump current
- Trigger Station Alarm
- Alarm severity
-
-
High pump current:
Select Yes to create a Station Alarm based on the High Pump Current alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Low pump current
- Trigger Station Alarm
- Alarm severity
-
-
Low pump current:
Select Yes to create a Station Alarm based on the Low Pump Current alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Backup float reached alarm
- Trigger Station Alarm
- Alarm severity
-
-
Backup float reached alarm:
Select Yes to create a Station Alarm based on the Backup float reached alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Sump Fail
- Trigger Station Alarm
- Alarm severity
-
-
Sump Fail:
Select Yes to create a Station Alarm based on the Sump Fail alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
Pump Fail
- Trigger Station Alarm
- Alarm severity
-
-
Pump Fail:
Select Yes to create a Station Alarm based on the Pump Fail alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.
High level alarm
- Trigger Station Alarm
- Alarm severity
-
-
High level alarm:
Select Yes to create a Station Alarm based on the High level alarm severity (critical or trip) and the configured Station Alarm notification rules. Select No otherwise.