OperateI/O States

Pump I/O Active States

  1
 2
3
Run indication
Run indication:

Set the active state for the Pump Run Indication digital input. Select Active HIGH if the input is ON to indicate a Pump is running, or select Active LOW when the input is OFF to indicate Pump is running.

Seal fail
Seal fail:

Set the active state for the Pump Seal Fail digital input. Select Active HIGH if the digital input is ON to indicate Pump Seal Fail, or select Active LOW when the digital input is OFF to indicate Pump Seal Fail.

Auto input
Auto input:

Set the active state of the Pump AUTO mode (HOA switch) digital input. Select Active HIGH if the digital input is ON for AUTO mode, or select Active LOW if the digital input is OFF to indicate Pump AUTO mode.

Hand input
Hand input:

Set the active state of the Pump HAND mode (HOA switch) digital input. Select Active HIGH if the digital input is ON for HAND mode, or select Active LOW if the digital input is OFF to indicate Pump HAND mode.

Run output
Run output:

Set the active state of the Pump Run digital output. Select Active HIGH to turn the Pump Run digital output ON to run the pump, or select Active LOW to turn the Pump Run digital output OFF to run the pump.

Temp / Overload
Temp / Overload:

Active polarity of Pump temperature or overload (combination) digital input. Default: Active HIGH = Fail.

Station I/O Active States

Phase fail
Phase fail:

Set the active state of the station Phase Fail digital input. Select Active HIGH when 24V is applied to the digital input, or select Active LOW when 0V is applied to the digital input to indicate Phase Fail status.

High level alarm float
High level alarm float:

Set the active state of the station High Level Alarm Float digital input. Select Active HIGH when 24V is applied to the digital input, or select Active LOW when 0V is applied to the digital input to indicate High Level Alarm Float status.

Intrusion alarm
Intrusion alarm:

Set the active state of the station Intrusion Alarm digital input. Select Active HIGH when 24V is applied to the digital input, or select Active LOW when 0V is applied to the digital input to indicate Intrusion Alarm status.

Flush Valve Output
Flush Valve Output:

Set the active state of the Flush Valve digital output. Select Active HIGH to turn the Flush Valve digital output ON when the Flush Valve is selected for operation by the FlowStation, or select Active LOW to turn the Flush Valve digital output OFF when the Flush Valve is selected for operation by the FlowStation.

Alarm Output
Alarm Output:

Set the active state of the Station Alarm digital output. Select Active HIGH to turn the Station Alarm digital output ON when a Station Alarm is active, or select Active LOW to turn the Station Alarm digital output OFF when a Station Alarm is active.

Sump Fail
Sump Fail:

Set the active state of the Sump Fail digital input. Select Active HIGH when 24V is applied to the digital input, or select Active LOW when 0V is applied to the digital input to indicate Sump Fail status.

Operator On-Site
Operator On-Site:

Set the active state of the Operator On-Site digital input. Select Active HIGH when 24V is applied to the digital input, or select Active LOW when 0V is applied to the digital input to indicate Operator On-Site status.